PANEL TROUBLE MESSAGES Look up what your panel is actually showing you. Forty five messages across Notifier and Simplex, each with what the message means and then an ordered list of what to check, most likely cause first. NO ANS leads with the device being twisted loose in its base, and tells you that several addresses going quiet together is an open circuit rather than a run of dead devices. INVREP leads with duplicate addressing, because two devices answering one poll is the classic cause and it produces exactly the wandering intermittent faults that eat a whole visit. On Simplex, Short Circuit clears itself once the short is gone, so it doubles as confirmation the repair worked. IDNAC Sig Unpowered has an order to it: correct the overcurrent first, then hardware reset, because the card will not restore while the fault is live. Earth fault tells you which polarity is at fault, which halves the search before you leave the panel room. Ground fault and earth fault entries carry the impairment steps and the rule that once a section comes off, it stays off, because faults sit on more than one section more often than people expect. More panels to follow.